Wednesday, February 29, 2012

Fault Listing for DDCC S320 for SAACKE Burner user with DDCC BMS

This fault has occurred for one of the following reasons:

F1 – Gas incorrect position
A drive positioning fault has occurred, which will cause a safety shutdown of the burner.

F2 -Oil incorrect position
During close position prove, when a drive stops at a position which is outside the close set position by more than five degrees.

F7 – Sec.air damper incorrect position
During purge position prove, when a drive stops at a position which is outside the close set position by more than five degrees

F9 – Prim.air damper incorrect position
During pre purge, ignition or post purge, when a drive moves from its set point.

F10 – Recirc.air damper incorrect position
During modulation, when a drive is not at its correct set point as defined by the commissioned fuel/air ratio for the selected profile.

F8 Variable speed incorrect position
A drive is defined as having moved from its set point if its positional error is more than 1o for 15s, or more than 5o for 1s.